FG16M16 - 0,6 / 1kV

Cca - s1b, d1, a1 According to European Construction Products Regulation CPR (EU) n.305/11

Reaction to fire REGULATION 305/2011/EU

  • Standard : EN 50575:2014+A1:2016 e EN 13501-6:2014
  • Class: Cca-s1b, d1, a1
  • Classification (CEI UNEL 35016): EN 13501-6
  • Heat and smoke emission during flame development: EN 50399
  • Vertical flame spread: EN 60332-1-2
  • Corrosive and halogenated gases: EN 60754-2
  • Smoke density: EN 61034-2

Reference standards :

Construction Products Regulation CPR).

CEI 20 - 13  -  CEI 20 - 67 - CEI UNEL 35324  - CEI EN 60332 -1-2 - 2014/35/UE - 2011/65/UE 

Cable description :

Flexible energy cables insulated with HEPR rubber of G16 quality under special thermoplastic sheathing of M16 quality

fire retardant and low emission of corrosive gases, halogen free.

Conductor :

Annealed red copper with flexible round cord CLASS 5.

 Core isolation :

HEPR high modulus rubber in G16 quality.

Sheath :

LS0H (Low Smoke 0 Halogen) thermoplastic coating in M16 quality

Sheath colour :

Green.

Labelling :

Impression/ink stamping on sheathing

depending on cross section every 1 m

Technical specifications :

Good behaviour at high temperatures, very low emission of fumes, toxic and corrosive gases, flame retardant, fire retardant and zero halogen.

Rated voltage: Uo/U: 0.6/1 kV c.a.  – 1,5  kV c.c.

Maximum operating temperature: 90° C

Minimum operating temperature: -15° C

Maximum short circuit temperature: 250° C

Installation conditions :

Minimum installation temperature: 0°C

Recommended minimum bending radius: 4 times the cable diameter

Maximum recommended tensile stress: 50 N/mm² of copper section

Packaging :

Hanks 100 metres - Wooden reel

Applications :

Cables used for supplying and transporting energy in residential buildings, places with a high number of people (schools, subways, discos, theatres, shopping centres, etc.), construction sites and industry.

Suitable for installation on walls, metal structures, ducts, pipes and similar, for use indoors, even in wet rooms, and outdoors. It can also be directly and indirectly buried.

Conductor number

n

Nominal

Section

 

Indicative

conductor diameter

 

Average thickness Insulation Maximum outer diameter Indicative weight

Kg/km

Electrical resistance at 20° C.

Maximum

 

1 x 10 4 0,7 9,40 152 1,91
16 5 0,7 10,4 215 1,21
25 6,2 0,9 12,4 315 0,780
35 7,6 0,9 13,4 395 0,554
50 8,9 1 15,7 550 0,386
70 10,5 1,1 17,4 750 0,272
95 12,5 1,1 19 970 0,206
120 13,8 1,2 21,2 1225 0,161
150 15,4 1,4 23,8 1545 0,129
185 17,5 1,6 26 1865 0,106
240 19,5 1,7 29,2 2410 0,0801
300 22 1,8 32 2950 0,0641